DLA Style 1 & 2

Enclosed Industrial Control Panel

NO. E-258342
Meets all Standards for Canadian Industrial Control Panels

The DLA Series Controller is used to operate remotely located 12-vdc latching solenoids for domestic water services in Healthcare Facilities or in a Drug Testing Laboratory.

This unit is provided with ISIMET latching circuit boards that permit a signal to latch the solenoids ON and OFF, controlling the water supply to the restroom facility.  In the case of patient rooms in a Healthcare Facility the ON circuit on the primary pcb enables the water to be turned ON and OFF either remotely or locally.  For Drug Testing Labs, the unit is intended to control the water flow to the restroom where drug samples are deposited. One board is designated to operate ON-OFF the water supply valves.  A secondary board permits solenoids to operate ON when the primary solenoids are OFF, thus allowing for drain-down of the piping. (MAX two solenoids per circuit board)

The unit conforms to all requirements of UL 508-A for Industrial Control Panels. 
Panic Button: Disengages the system; requiring key activation.
Key Switch:  Activates the system each time a circuit is to be engaged. (Optional Push Button)
Control Switch: Activates a circuit with key activation or deactivates to OFF.
Panel Mounted LEDs: Indicates the circuit is active.
Integrated operating system inputs including building automation.
Integrated notification output circuits.

* All Standard Styles are provided with Panic Button Assembly


 

Style 1 is limited to 2 Solenoids W/ PCB Configuration 1, 2, or 3 only.

Style 2 is limited to 4 Solenoids W/ PCB Configuration 1, 2, or 3 only.

Styles 1 & 2 are provided W/ Monitoring Output Circuits. Except Style 1 W/ PCB Configuration 3 that is provided W/ 2 Switches

Style 3 is intended for use in multi-patient room environments where water supplies are to turn ON & OFF remotely.

PCB Configuration 2 is intended for use with ISIMET S-Series Enclosure having Latching Solenoids and Pulse PCB included.

All Solenoids for DLA Units should utilize ISIMET 12 VDC Latching Coils.

PCB Configurations 4, 6, & 8 also indicate the number of switches for specific patient rooms.

 

Mounting Variations:  

Casework: Wall Box is provided with flange to permit mounting from the outer casework surface. (Styles 1 & 2 only)

Flush Wall Mount: Wall Box is provided with a wall mounting flange and hardware.

Surface Mount: Wall Box is provided with a wall mounting flange and hardware.

                             *A Stainless Steel skirt is provided to conceal the wall box for Styles 1 & 2.

Style

# Output Circuits

Transformer

Switch\

Breaker

Output Rating

(Standard)

Pulse Output

1 & 2

1 @ 24 vac

3 amp

5 amp

2 amp @ 24 vac

1-2 @ 12 vdc
Per LA PCB

3

2 @ 24 vac
Per LA PCB

4 amp
Per 2 LA PCB

15 amp

2 amp @ 24 vac

2 @ 12 vdc
Per LA PCB


 


 

Styles 1 & 2 are designed for single room control of water supply to patient rooms in Healthcare Facilities and Drug Testing Laboratories.

Integral 5 amp rated circuit service switch / j-box / transformer / pcb
Control Panel - Stainless Steel 16 gauge W/ removable concealed hinge and gasket.
Captive screws secure panel to enclosure.
Wall Box Enclosure – 16 gauge powder coated sheet metal
Enclosure Size - 6.0 X 14.25X 4
Unit performs as a single circuit Controller of water services W/ monitoring beacon output.


 

ISIMET Utility Controllers and Companion Enclosures
Two Hour Fire Rating

UL Test #1479

All ISIMET Utility Controllers, Enclosures and Accessories can be certified for two-hour fire rating.  Working closely with the industry leader in fire rated materials, ISIMET can offer our enclosures with a one-half inch fire rated blanket.  This blanket that is adhered to the outer surface of the enclosure will enable the installer to incorporate the ISIMET product into a fire rated wall without the need for additional blanket or other rated material.

To specify a unit as “Fire Rated” use the following nomenclature:

Add to the ISIMET Part Number:  Prefix “F2” for all Utility Controllers, Companion Enclosures and Accessories.  Model numbers are for example only.

UtC-F2-12X9 indicates a four-circuit Utility Controller with fire blanket.

LA-F2-1212 indicates a wall mounted LA Series with fire blanket.

FLA-F2-2235 indicates a wall mounted FLA Series with fire blanket.

E-F2-1212 indicates a twelve-circuit E-Series with fire blanket.

S-F2-1211-3-3/4-K indicates a three-station S-Series with fire blanket.

MLA-F2-1-B indicates a Monitoring Beacon with fire blanket.

All components utilized in this “Fire Rating” will be provided with additional instructions for installation in order to insure that the rated material and process is not violated or damaged during installation.  Fire caulking as well as foil tape and extra blanket material is included for all components except for accessories.  Accessories are provided with foil tap and extra blanket only.  Fire caulking will need to be field provided.  Enclosure Sizes limited to 24” X 24” X 8” and smaller.








Fire Rating Field Instructions