FLA Series

FLA Series
Fire House Controller

Dual Output Circuit  Ver 4.6 pcb

ENCLOSED INDUSTRIAL CONTROL PANEL   NO. E-258342
Meets all Standards for Canadian Industrial Control Panels

Application:
The FLA Series Controller operates as a dual output controller to operate fuel gas outlets as well as electrical devices located within the kitchen in a Fire Station.  Input terminals equipped with a delay function will turn OFF all connected appliances when a notification signal is received for a fire or other emergency response.

The Alarm Signal initiated by the Fire Response System for the Fire Station will automatically shut down the kitchen’s utilities and devices that are operated by the Controller when this System is integrated with the FLA Unit.

A Time Delay circuit on the Version 4.6 FLA Controller allows for up to ten (10) minutes to elapse before shutdown occurs.  This delay may prevent a kitchen shutdown in the event that the Alarm is withdrawn during this delay period.

Further, if the response is not such that normal activities at the station must be altered for some of the staff, an OverRide switch on the unit will stop the shutdown.

A 10 amp, 120 vac circuit is available to operate the wall plug at the gas oven.


 

ISIMET FLA Series Controller

Product Description

The FLA Series Controller operates as a dual output controller to operate fuel gas outlets as well as electrical devices located within the kitchen in a Fire Station. A 10 amp 120 v output is provided at the unit in order to make electrical connect to the range electrical plug used for electronic ignition.  Input terminals equipped with a delay function will turn OFF all connected appliances when a notification signal is received for a fire or other emergency response.

The Alarm Signal initiated by the Fire Response System for the Fire Station will automatically shut down the kitchen’s utilities and devices that are operated by the Controller when this System is integrated with the FLA Unit.

A Time Delay circuit on the Version 4.6 FLA Controller allows for up to ten (10) minutes to elapse before shutdown occurs.  This delay may prevent a kitchen shutdown in the event that the Alarm is withdrawn during this delay period.

Further, if the response is not such that normal activities at the station must be altered for some of the staff, an OverRide switch on the unit will stop the shutdown. 

Typical Controlled Services
Electrical and Fuel Gas

 

Enclosure Specifications
Control Panel - Stainless Steel 16 gauge - 8.375” x 14.5”
Control Panel Dimensions Wall Box – 16 gauge powder coated sheet metal - 6.0” x 12.25” x 4.0”

Note: 120 VAC @ 15 Amp Supply Voltage required for Controller

Available Integration Inputs and Outputs Dry-Contact


24V
AC/DC

5 VDC
Remote Panic Input X
Alarm Input   X X

 

Styles Output Circuits Transformer Panel Fuse PCB Fuse 1 PCB Fuse 3 Output Rating
FLA-2XX5

1 @ 120 VAC;
1 @ 24 VAC
3 Amp 15 Amp 3 Amp 500 mAmp 1 x 10 Amp Max @ 120VAC (Resistive)
1 x 2 Amp Max @ 24 VAC
FLA-2XX6

1 @ 120 VAC;
1 @ 24 VAC

3 Amp 15 Amp 3 Amp 500 mAmp 1 x 10 Amp Max @ 120VAC (Resistive)
1 x 1.5 Amp Max @ 24 VAC

 


 

Control Panel - Stainless Steel 16 gauge          

                            8.375 X 14.5

 

Wall Box – 16 gauge plated sheet metal 

             6.0 X 11.875 X 4.0

                    * all dimensions are in inches

Output Reset Switch - (Where Provided)

             Reset Switches are specifically rated to

             accommodate output load requirements.

 

Style:  Units are intended for use as a Safety Shut OFF for Kitchens in Fire Stations and similar applications.

 Single Source – Unit provides an Operation Station with control over up to two solenoid valves to operate fuel gas as well as 120 vac convenience outlets.  A single switch controls all output circuits.

  • All Standard Styles are provided with Panic Button Assembly and Push Button Reset.
  • Units may be ordered with Keyed Reset.
  • Optional Alarm OverRide Switch allows users to Stop an Alarm Signal from turning OFF the Unit.
  • A Remote Operator can be added in order to control a outdoor gas grill.
  • 3 amp Transformer rating.

Styles

# Output Circuits

Switch/

Breaker

120 V Output

Fuse

Pcb

Fuse 1

Relays

Solenoid Outputs

FLA –2XX5

 

1 @ 120 vac

1 @ 24  vac

 

15 amp

15 amp

3 amp

15 amp @ 120 vac

2 amp @ 24 vac

2 @ 0.2 amp @ 120 vac

2  @ 1 amp @ 24 vac

 

FLA –2XX6

1 @ 120 vac

1 @ 24  vac

15 amp

15 amp

3 amp

15 amp @ 120 vac

1.5 amp @ 24 vac

1 @ 1.5 amp @ 120 vac

1  @ 1.5 amp @ 24 vac

 


 

ISIMET Utility Controllers and Companion Enclosures
Two Hour Fire Rating

UL Test #1479

All ISIMET Utility Controllers, Enclosures and Accessories can be certified for two-hour fire rating.  Working closely with the industry leader in fire rated materials, ISIMET can offer our enclosures with a one-half inch fire rated blanket.  This blanket that is adhered to the outer surface of the enclosure will enable the installer to incorporate the ISIMET product into a fire rated wall without the need for additional blanket or other rated material.

To specify a unit as “Fire Rated” use the following nomenclature:

Add to the ISIMET Part Number:  Prefix “F2” for all Utility Controllers, Companion Enclosures and Accessories.  Model numbers are for example only.

UtC-F2-12X9 indicates a four-circuit Utility Controller with fire blanket.

LA-F2-1212 indicates a wall mounted LA Series with fire blanket.

FLA-F2-2235 indicates a wall mounted FLA Series with fire blanket.

E-F2-1212 indicates a twelve-circuit E-Series with fire blanket.

S-F2-1211-3-3/4-K indicates a three-station S-Series with fire blanket.

MLA-F2-1-B indicates a Monitoring Beacon with fire blanket.

All components utilized in this “Fire Rating” will be provided with additional instructions for installation in order to insure that the rated material and process is not violated or damaged during installation.  Fire caulking as well as foil tape and extra blanket material is included for all components except for accessories.  Accessories are provided with foil tap and extra blanket only.  Fire caulking will need to be field provided.  Enclosure Sizes limited to 24” X 24” X 8” and smaller.








Fire Rating Field Instructions